1. Module Overview
AN5800/10 series vibration monitoring module receives signals from two magneto-electric tachometric sensors or Proximity sensors; the original signals from the sensor are converted into digital signals by a signal interface unit; the digital signals are transmitted to an embedded microcontroller unit (MCU), and are then identified, judged, processed and compared by software and output by output units, thus implementing online monitoring and protection of device vibration.
2. Purpose
● Online monitoring and protection of rotary machine bearing vibration;
● Online monitoring and protection of rotary machine shaft vibration;
● Online monitoring and protection of rotary machine Throw.
3. Functions
● Digital display unit: To display real-time value;
● Serial communication interface: Parameter configuration and digital signal bus communication through AN5800 / CFG configuration software;
● Standard signal output: 4-20mA;
● On-off output: two-stage alert normally open/closed contact output;
● LED indicator: To display various statuses;
● Buffer interface: The front panel BNC connector and rear terminal buffer output (Sensor original signal) are convenient to connect the data acquisition system to collect dynamic signals.
4.Features
● Perfect self-inspection and diagnosis function; when a failure occurs, current output is 0mA, and "Not Ok" LED on the panel is on;
● Embedded microcontroller unit (MCU); an E2PROM data storage unit (for important parameters) and a FLASH process program storage unit are integrated in the chip;
● Power unit: a DC-DC/AC-DC module power supply realizes ultra-width power input and isolated output;
● Use forward board and back board plug-in module type structure design, after the board (power supply and relay output) and the former board (signal processing, the host) physical isolation, through case motherboard more redundant connectors (needle) in parallel connection, stable and reliable.
5. Application
Application Fields:
● Power plants (thermal, hydro, nuclear and wind);
● Metallurgy (steel mills and aluminium manufacturers, etc.);
● Petrochemical engineering (refining and chemical, coal chemical industry and chemical fertilizers, etc.);
● Cement;
● Papermaking;
● Mine (coal and iron mines);
● Hydraulic engineering (reservoirs and pump stations), etc.
Monitored equipment:
● Steam turbines;
● Compressors;
● Motors
● Water pumps;
● Gearboxs
● Water turbines;
● Air blowers;
● Coal-breaker;
● Coal-mill;
● Rotary machines like fans.
6. Technical Specifications
● Sensors:
Magneto-electric Velocity sensor:
Inertial sensor, no power supply
Sensitivity: 20 mV/mm/S(500mV/in/s).
Piezoelectric acceleration sensor:
ICP type, 24V / 4mA constant current source power supply
Sensitivity: 100mV/g
Piezoelectric velocity sensor:
ICP type, 24V / 4mA constant current source power supply
Sensitivity: 4mV/g
Proximity sensor: φ8 probe
Sensitivity: 7.87mV/μm (200mV/mil)
Output voltage: -2 ~ -18VDC;
GAP voltage: -10VDC.
● Range of measurement:
Displacement: 0~999μm(Pk-Pk); Resolution: 1μm; Precision: 0.5%±1μm.
Velocity: 0~99.9mm/S(rms); Resolution: 0.01mm/S; Precision: 0.5%±0.01mm/S.
Acceleration: 0~9.99g(Pk); Resolution: 0.01g; Precision: 0.5%±0.01g.
● The frequency range
Piezoelectric Sensor: 0.5~15KHz;
Magneto-electric Sensor:
Standard: 10~1000Hz
Low frequency: 5~1000Hz
Ultra-low frequency: 0.5~100Hz;
Proximity Sensor:0~10 KHz;
● Power supply of module:
DC supply: 24VDC (18~36V);
Module power dissipation: less than 5W
● Standard signal output:
Standard current, active 4~20mA (responding to the upper limit of full range;
Driving load: ≤750Ω
Valid transmission distance: ≤ 300 meters(1000 feet)
● Relay output:
Two-level high(Alert,Danger)programmable setup and normally open/closed dry contact output, available for setting full range, error ≤0.1%;
Insulation resistance: ≥1000MΩ;
Contact capacity: 2A/30VDC, 1A/220VAC; double-pole double-throw (DPDT);
Alarm time delay: 0.1~60S, default value: 0.5S;
Alarm latching: programmable setup, (non- latching by default).
● Physical property:
Before the board:
Size: 248(L)×40(W)×262(H)mm;9.8(L)×1.5(W)×10.3(H)in;
Weight: 0.6kg.
After the board:
Size: 128(L)×40(W)×262(H)mm;9.8(L)×1.5(W)×10.3(H)in;
Weight: 0.3kg.
● Environmental restrictions:
Operating temperature: 30℃~+65℃(-22oF~+150 oF)
Storage temperature: -40℃~+85℃(-40oF~+180 oF)
Relative humidity: 0~95% (non-condensing).
● Executive standards
The United States Petroleum Association Standard: API 670;
Safety certificate: C E;
Anti-electromagnetic interference: EMC\ LVD;
Refer to EN55011\ EN 61010\EN50081\EN50082
7. Ordering information
AN5800/11/12/13—bearing vibration/shaft vibration/throw
AN5800/11-AXX-BXX-CXX-DXX
AN5800/12-AXX-BXX-CXX-DXX
AN5800/13-AXX-BXX-CXX-DXX
Standard Configuration Model:
Bearing vibration:
AN5800/11-00-01-00-00(velocity sensor input, velocity output)
AN5800/11-00-00-00-00(velocity sensor input, displacement output)
Bearing vibration:(ultralow frequency)
AN5800/11-00-01-02-00(velocity sensor input, displacement output)
AN5800/11-00-00-03-00(displacement sensor input, displacement output)
Shaft vibration:AN5800/12-00-00-01-00
Throw: AN5800/13-00-03-01-00
A: Channel selection:
00—2 channel
01—1 channel (channel A on top of module by default)
B: Measurement type:
00—Displacement:0~999μm(Pk-Pk)
01—Velocity:0~99.9mm/s (rms)
02—Acceleration:0~9.99g(Pk)
03—Throw:0~999μm(Pk-Pk)
C: Type of external sensor:
00—AN1930 velocity sensor
01—AN1808 proximity sensor (φ8 probe)
02—AN1931 frequency velocity sensor
03—AN1931 frequency displacement sensor
04—AN1940 piezoelectric acceleration sensor (ICP)
05—AN1940 piezoelectric velocity sensor (ICP)
D: Relay output selection (DPDT)
00—3 relays output(Alert、Danger、Not-ok)
01—2 relays output(Alert、Danger)
02—1 relay(Alert)
03—No relay output